PT Chart
Saturation pressure (psig) ↔ saturation temperature (°F). Linear interpolation between chart rows, 30 to 125°F only.
Chart (psig)
Superheat & Subcooling
Enter the gauge pressure and the line temperature. Saturation comes from the PT chart in this app.
Superheat (suction side)
Subcooling (liquid side)
Quick Formulas & Targets
From the cards in 55 HVAC Visual Cards.
Measured at the suction line. For R-454B, read saturation from the DEW column. Near-zero superheat means liquid may be reaching the compressor.
Measured at the liquid line near the service valve. For R-454B, read saturation from the BUBBLE column. Target is on the rating plate.
Carrier/Bryant rule. Check airflow first; charge with the system running at least 15 minutes and within the manufacturer's charging conditions.
Carrier, Rheem and Lennox all call for 500 microns. Read the micron gauge far from the pump and run the decay test in the unit's manual.
Rheem guideline. Lennox: target temperature drop is based on return-air dry bulb and wet bulb (±3°F).
Goodman method, 60 Hz. Compare with the tolerance printed on the capacitor. Live test: CAT III meter and PPE.
30 visual cards: read unit wiring diagrams, wire thermostats for AC, heat pumps, two-stage and dual fuel, add a C wire, trace the safety chain, wire PSC and ECM motors, and troubleshoot no-cooling calls.